| ASW* |
| TECHNICAL
DATA |
| Power
supply |
9 to 30 Vdc or 12 to 24 Vac (-10% to +15%), 50/60 Hz
ASWC112000: 24 Vac/dc (-10% to +15%), 50/60 Hz |
| Operating Conditions |
ASWH*: 14°F to 158°F, 10 to 90% rH non-condensing
ASWT*: 14°F to 158°F, 10 to 90% rH non-condensing
ASWC*: 32°F to 122°F, 10 to 90% rH non-condensing |
| Storage Conditions
| -4°F to 158°F, <90% rH non-condensing |
| Range
| ASWH*: 10 to 90% U.R.
ASWT*:14°F to 158°F
ASWC*:32°F to 122°F, 10 to 90% rH non-condensing |
| Precision
| ASWH*: 77°F ± 3%, 32°F to 122°F ±6%
ASWT030*: 77°F ±0.36°F, 14°F to 158°F ±1.26°F
ASWT011*: 77°F ±0.45°F, 32°F to 122°F ±0.9°F
ASWC110*: Temperature: 77°F ±0.72°F, 32°F to 122°F ±0.9°F Humidity: 77°F ±3%, 32°F to 122°F ±6%
ASWC111*: Temperature: 77°F ±0.45°F, 32°F to 122°F ±0.9°F Humidity: 77°F ±3%, 32°F to 122°F ±6%
ASWC112*: Temperature 77°F ±0.72°F, 32°F to 122°F ±2.16°F Humidity: 77°F ±3%, 32°F to 122°F ±6% |
| Output Signals
| ASWH*: 0 to 1 V; 4 to 20 mA
ASWT*: NTC res. (compatible with Carel controllers) or 0 to 1 V; 4 to 20 mA
ASWC*: 0 to 1 V; 4 to 20 mA
ASWC112*: 0 to 10 V; 0 to 1V; 4 to 20 mA |
| Time Constant
| ASWH*: 60 s (still air); 20 s (9.8 ft/s)
ASWT030*: 250 s (still air); 25 s (9.8 ft/s)
ASWT011*: 300 s (still air); 110 s (9.8 ft/s)
ASWC*: Temperature: 250 s (still air); 25 s (9.8 ft/s) Humidity 60 s (still air); 20 s (9.8 ft/s) |
| Index of protection |
IP30 |
|
|