Industrial and Commercial Humidifiers
    and OEM HVAC/R Controls

 
AIR CONDITIONING CONTROLS REFRIGERATION CONTROLS HUMIDIFIERS EVAPORATIVE COOLING
KSA Helpful Links 1tool Case Studies Remote Management BMS Interfaces
 
EVD Evolution - Electronic Expansion Valve Driver Specifications
» back » part numbers » specification » literature
 
TECHNICAL SPECIFICATIONS
EVD Evolution
EVD Evolution Twin
Power Supply
24 Vac (+10/-15%)50/60 Hz to be protected by external 2 A type T fuse. Use a dedicated class 2 transformer (max 100 VA). Lmax=5m
  24 Vac (+10/-15%)50/60 Hz to be protected by external 2 A type T fuse. Use a dedicated class 2 transformer (max 100 VA). Lmax=5m
Power input
30 VA
  35 VA
Emergency Power Supply
22 Vdc +/-5% (If the optional EVBAT00400 module is installed.
  22 Vdc +/-5%. (If the optional EVBAT00400 module is installed). Lmax-5m

Insulation between relay
output and other outputs

6 mm in air, 8 mm on surface
  reinforced; 6 mm in air, 8 mm on surface; 3750 V insulation.
Motor Connection
4 wire shielded cable AWG 18/22, Lmax=10 m
  4-wire shielded cable AWG 22, lmax 10 m or AWG 14, lmax = 50 m
Digital input connection
Digital input to be activated from voltage-free contact or transistor to GND. Closing current 5 mA. Lmax=30 m
  Digital input to be activated from voltage-free contact or transistor to GND. closing current 5 mA; Lmax<30m
Relay output
normally open contact, 5A, 250 Vac resistive load, 2A, 250 Vac inductive load (PF=0.1), Lmax=10m
  normally open contact; 5A, 250 Vac resistive load; 2A 250 Vac inductive load (PF=0.4; Lmax-50m; UL:250 Vax, 5A resistive, 1A FLA, 6A LRA, pilot duty D300.30000 cycles
Power to active sensors
(V REF)
+5Vdc+/-2% or 12Vdc+/-10% depending on type of sensor set   +5Vdc+/-2% or 12Vdc+/-10% depending on type of sensor set
RS485 serial connection
Lmax=1000m, shielded cable
  Lmax=1000m, shielded cable
TLAN Connection
Lmax=30m, shielded cable
  Lmax=30m, shielded cable
pLAN connection
Lmax=500m, shielded cable
  Lmax=500m, shielded cable
Assembly
DIN rail
  DIN rail
Connectors
plug in, cable size 0.5 to 2.5 mm2
  plug in, cable size 0.5 to 2.5 mm2
Dimensions
length x height x width = 70x110x60
  length x height x width = 70x110x60
Operating conditions
14 to 1400 F; <90% rH non-condensing
  14 to 1400 F; <90% rH non-condensing
Storage conditions
-4 to 158 0 F, humidity 90% rH non-condensing
  -4 to 158 0 F, humidity 90% rH non-condensing
Index of protector
IP20
  IP 20
Resistance to heat and fire
Category D
  Category D
Immunity against voltage
surges
Category 1
  Category 1
Type of relay action
1C microswitching
  1C microswitching
Insulation class
2
  2
Software class and structure
A
  A
Conformity
Electrical safety: EN60730-1, En 61010-1
  Electrical safety: EN60730-1, En 61010-1, UL873
Electromagnetic compatibility: EN 64000-6-1, EN 64000-6-2, EN61000-6-3, EN 641000-6-4, EN1000-3-2, EN55014-1, EN55014-2, EN61000-3-3.
  Electromagnetic compatibility: EN 64000-6-1, EN 64000-6-2, EN61000-6-3, EN 641000-6-4, EN1000-3-2, EN55014-1, EN55014-2, EN61000-3-3.
 
 