Industrial and Commercial Humidifiers
    and OEM HVAC/R Controls

 
AIR CONDITIONING CONTROLS REFRIGERATION CONTROLS HUMIDIFIERS
HumidCalc Rep Locator Product Demonstrations Literature Product Registration Secure Rep Area
 
 Electrode Steam Humidifier
 
» product overview
» product data
» Literature
Models humiDisk65 humiDisk10
Steam production (lb/hr) 1.9 lbs/hr up to 14.3 lbs/hr 2.2 lbs/h at 2330V/50hz; 2.6 lbs/hr at 110v/60hz
Power supply 230V, 50Hz - 11V, 60HZ 230V, 50HZ - 110 V, 60Hz
Air flow 165 cfm 47 cfm
Water inlet pressure 14.5 to 145 psi  
Water tank 0.012 lbs 0.12 lbs
Index of protection IPX4 IPX4
Ambient condition limits (without anit-freeze heater) 34 to 95 °F, 0 to 100% RH non-condensing
Ambient condition limits (wth anti-freeze heater) 28 to 95 °F, 0 to 100% RH non- condensing
Water temperature limit 34 to 122 °F
Water total hardness limits* 30 °fH, 300 ppm CaCO3
Water conductivity limits 100 to 1200 µS/cm

*not lower than 200% of CI- in mg/l

The quantity and quality of the minerals dissolved in the water affects the frequency of the routine maintenance operations and the amount of dust generated. For best operation, use demineralized water (not softened, as this does not reduce the content of mineral dissolved in the water).At any rate, it is suggested to follow the specifications of the UNI 8884 standard, "Characteristics and treatment of the water in cooling and humidification circuits", conductivity <100 µS/cm; total hardness <5 °fH (50ppm CaCO3).

 


 
 