TECHNICAL DATA 
Power supply (control with terminal connected) 22/40Vdc and 24Vac +15% 50/60 Hz. Maximum consumption P=20W 
Operating conditions  14-140F; 32-122F versions with built-in display; 90% rH non-condensing
Storage conditions -4 - 158F; 90% rH non-condensing
Mechanical protection IP20 - IP40 front panel only
Classification according to protection against electric shock To be incorporated in Class I and /or II appliances
PTI of the insulating materials 250V
Period of electric stress across insulating parts Long
Type of relay action 1C
Type of disconnection or micro switching Micro switching
Category of resistance to heat and fire Category D (UL94 - V0)
Immunity against voltage surges Category 1
Aging specifications (operating hours) 80,000
Number of automatic operating cycles  100,000 (EN 60730-1); 30,000 (UL873)
Software class and structure Class A
COMPARATIVE CHART

PCO2*Small

PCO2*Medium
PCO2*Large
Maximum flash memory capacity 6MB

6MB

6MB
Real time clock standard
standard
standard
BUS expansion standard
standard
standard
Programming key optional
optional
optional
Built-in display optional optional optional
LED indicators (custom display port) optional optional optional
I/O expansion only with built-in display only with built-in display standard
Multi-language standard
standard
standard
Black box (data logging) standard

standard

standard

Carel compatible standard (require Comm. board) standard (require Comm. board) standard (require Comm. board)
Metasys® compatible standard (require Comm. board) standard (require Comm. board) standard (require Comm. board)
Modbus® compatible standard (require Comm. board) standard (require Comm. board) standard (require Comm. board)
LonWorks® compatible standard (require Comm. board) standard (require Comm. board) standard (require Comm. board)
BacnetTM compatible optional optional optional
TCP/IP compatible (SNMP-HTTP) optional optional optional
pLAN standard standard standard
Modem ready standard standard standard
GSM modem ready standard standard standard
SMS ready standard standard standard
Maximum number of analog inputs 5 8 10
PT1000 inputs 2 2 4
0-10Vdc inputs 3 6 6
0-1Vdc inputs 3 6 6
4-20mA or 0-20mA inputs 3 6 6
NTC inputs 5 8 10
0-5 Vdc ratiometric inputs not available not available not available
AIN setting by software standard standard standard
AIN setting by dip-switch not available not available not available
Maximum number of digital inputs 8 14 18
24Vac/Vdc inputs 8 14 18
230Vac/Vdc inputs not available 2 4
Free contact inputs 2 2 4
Maximum number of analog outputs 4 4 6
0-10Vdc outputs 4 4 6
PWM outputs not available not available not available
Maximum number of digital outputs 8 13 18
SPST relay outputs 7 10 13
SPDT relay outputs 1 3 5
SSR outputs 1 2 3
Microprocessor architecture  16 bit 16 bit 16 bit