  pCO3 (I/O Board) Specification
 pCO3 (I/O Board)
mounting drawing electric drawing dimension drawing overview drawing
Technical Data
Power supply 24 Vac (±15%), 50/60 Hz or 22 to 40 Vdc
Power input 40 VA or 15 W
Operating conditions 14 to 140°F (-10 to 60°C), 90% RH non-condensing
Storage conditions -4 to 158°F (-20 to 70°C), 90% RH non-condensing
Index of protection IP20 - front panel IP40
» product overview
» part number
» accessories
» specification
» literature
 
 Model comparison
Model PCO3*S PCO3*M PCO3*L PCO3*XL PCO3*XL
ver.NO
PCO3*XL
ver.NC
Maximum flash memory capacity 6 MB 6 MB 6 MB 6 MB 4 MB 4 MB
Nand Flash optional optional optional optional optional optional
Real time clock standard standard standard standard standard standard
pLAN standard standard standard standard standard standard
opto-isolated pLAN optional optional optional optional optional optional
tLAN optional optional optional optional optional optional
Pre-set for programming key standard standard standard standard standard standard
PGD0 built-in display optional optional optional optional optional optional
PGD1 built-in display optional optional optional optional optional optional
Built-in display 4x20 - - - - - -
LED indicators optional optional optional optional optional optional
I/O expansion optional optional standard standard standard standard
Black Box standard standard standard standard standard standard
CAREL compatible standard standard standard standard standard standard
Modbus® compatible standard standard standard standard standard standard
LonWorks® compatible optional optional optional optional optional optional
BACnet™ compatible optional optional optional optional optional optional
TCP/IP compatible optional optional optional optional optional optional
CANbus compatible optional optional optional optional optional optional
MP-BUS Belimo optional optional optional optional optional optional
modem, modem GSM, SMS ready standard standard standard standard standard standard
Maximum number of analogue inputs 5 8 10 8 8 10
PT1000 inputs 2 2 4 2 2 4
0 to 10 Vdc inputs 3 6 6 6 6 6
0 to 1 Vdc inputs 3 6 6 6 6 6
4 to 20 mA or 0 to 20 mA inputs 3 6 6 6 6 6
NTC inputs 5 8 10 8 8 10
0 to 5 Vdc ratiometric inputs 3 6 6 6 6 6
AIN setting by software standard standard standard standard standard standard
AIN setting by dip-switch - - - - - -
Maximum number of digital inputs 8 14 18 14 14 14
24 Vac/dc inputs 8 14 18 14 14 14
230 Vac/dc inputs - 2 4 2 2 2
Free contact inputs 2 2 4 2 2 4
Maximum number of analogue outputs 4 4 6 4 4 4
0 to 10 Vdc outputs 4 4 6 4 4 4
PWM outputs - - - - - -
Maximum number of digital outputs 8 13 18 29 29 27
SPST relay outputs 7 10 13 26 26 24
SPDT relay outputs 1 3 5 3 3 3
Maximum number of SSR output 2 4 6 6 6 6
 
 