Industrial and Commercial Humidifiers
    and OEM HVAC/R Controls

 
AIR CONDITIONING CONTROLS REFRIGERATION CONTROLS HUMIDIFIERS EVAPORATIVE COOLING
KSA Helpful Links 1tool Case Studies Remote Management BMS Interfaces
 
pGD
panel or wall mounting pCO® system user interfaces 
pGD TECHNICAL DATA 
Power supply from pCO® through telephone cable or external source 18 to 30 Vdc through TCONN6J000 
Power Input 0.8 W
Operating Conditions - 4° to 140°F, <90% rH non-condensing
Storage Conditions - 4° to 158°F, <90% rH non-condensing
Text Mode 4 rows x 20 columns (font sizes 5x7 and 11x15 pixels) or
2 rows x 10 columns (font size 11x15 pixels) or
mixed mode
Character Height .18 inches (font size 5x7 pixels) or
.35 inches (font size 11x15 pixels)
Maximum Distance from the Controller 164 Ft. with telphone cable,
1640 Ft. 5 Inches with AWG22 twisted pair cable and TCONN6J000 (to reach the maximum length use a bus layout with branches not exceeding 16 Ft. 4 Inches)
Index of Protection

IP65 with panel mounting and IP40 with wall mounting

 

» product overview
» part number
» accessories
» specification
» connectivity
» literature

 

 
 
 
Copyright © 2006 CAREL USA. All Rights Reserved.
Home     Contact Us    Careers    Sitemap | Standard Terms and Conditions
Air Conditioning Controls |  Refrigeration Controls  | Electronic Expansion Valves  | Air Conditioning/Refrigeration Sensors & Accessories  