SUGGESTED ENGINEERING SPECIFICATIONS

SD2000 ELECTRONIC STEAM HUMIDIFIERS

 

15781 HUMIDIFIERS

 

I.                GENERAL

 

A.    Scope

 

1.               Furnish and install as indicated on the drawings and plans, in-duct [space] electronic steam humidifiers.

 

2.               Furnish owner's manuals and blueprints covering installation, start up, maintenance and operating instructions, complete in every way to permit efficient operation and maintenance of the system.

 

3.               Manufacturer shall warrant the system to be free from defects in materials and workmanship for a period of 2 years after the sale.

 

4.               Capacities are as shown on the drawings and plans.

 

II.              PRODUCT

 

A.    Humidifiers

 

1.               The humidifiers shall be of the self generating electrode type, electrically producing atmospheric steam in a plastic cylinder without the use of immersion type electric heating elements.

 

2.               The humidifier cabinet shall be constructed of 16 gauge steel, painted or coated inside and out to protect against corrosion and to be aesthetically pleasing.

 

3.               The electrodes shall be constructed of expanded low carbon steel, zinc plated and dynamically formed for precise current control and cleanability. Electrical connection to the electrodes shall be by screw down connectors. Spark plug type connectors can loosen and are therefore unacceptable.

 

4.               The steam generating cylinder shall be constructed of a UL listed plastic having at least a 94HB safety rating, and being of a design to withstand cleaning by light acids and reuse.

 

5.               The steam generating cylinder shall have twin cylinder full electrodes operating as an independent circuit from the main power electrodes. No artificial neutral circuits shall be required. Additionally, the cylinder full electrodes shall be used to detect foaming of the water.

 

6.               Units producing over 30 lbs/hr capacity shall incorporate a power drain pump instead of drain solenoid to provide for more efficient flushing of the cylinder.

 

7.               All internal electrical controls and components shall be prewired to appropriately marked terminals for field connection. All internal components and the cabinet shall be properly grounded and shielded to prevent any line or radiative interference.

 

8.               The humidifiers shall incorporate a true microprocessor control providing the following functions:

 

a)                        Automatic flushing of the steam generating cylinder based on conductivity, not just amperage draw, to extend the life of the electrodes. The humidifier shall read AND display the incoming water conductivity.

 

b)                        Pushbutton selection of drainage under power or timed drain to eliminate current leakage through the drain.

 

c)                         Digital LCD Display of:

 

Incoming water conductivity

Electric current draw in Amps

Output of the humidifier

Selected output limit

Model No. and unit configuration

[Display of sensed %RH on unit] [in CDH, CDD models]

[Display of %RH setpoint] [in CDH, CDD models]

[Display of differential] [in CDH, CDD models]

 

9.               The humidifier shall have the AFS anti-foaming system to allow automatic detection and correction of water foaming. The humidifier shall be capable of operating on water qualities ranging from 50-1500 micromhos conductivity. Additionally, the AFS system must be capable of working on water treated with phosphates.  Softened water should not be used.

 

10.           The humidifier microprocessor control shall incorporate complete diagnostics, including the following alarms and prealarms which shall be shown on the LCD display:

 

High electric current in the steam cylinder

Low current electrolysis condition

Reduced steam output, unable to reach setpoint

High water level in cylinder

Humidity sensor defective

Water foaming in cylinder

Improper cylinder fill rate

Improper cylinder drain rate

Diagnostic memory test fail

All prealarms shall be self-correcting.

 

11.           The humidifiers shall be configured for CDC-On/Off

[CDP-Proportional]

[CDH-Proportional with humidity readout]

[CDD-Proportional with dehumidifier output] operation.

 

12.           Each humidifier shall have a built in serial adapter connection allowing future interface to computer or EMS systems if required. This shall be complete serial communication of all setpoints, status and alarms, not just acceptance of a modulating signal. Manufacturer shall have available graphic monitoring/control software capable of running in Windows.

 

13.           [Optional] The humidifiers shall be provided with a direct [remote] mount Room Distribution Unit for direct discharge of humidifying steam into the area to be humidified.

 

14.           [Optional] The humidifiers shall be provided with a factory mounted condensate pump to pump the drain water to an overhead or remote drain.

 

B.    Installation

 

1.               The humidifiers shall be installed as per the plans and drawings, connected to a potable cold water feed line, and a hot water drain line and electrical service sized appropriately for the maximum current draw of the unit. All wiring shall be in accordance with national and local electrical codes.

 

2.               Manufacturer shall supply a duct mounted air flow proving device to prevent system operation on loss of air flow.

 

3.               Manufacturer shall supply a duct mounted high limit humidistat to prevent condensation in the duct.

 

C.    General Operating Sequence And Control

 

1.               All humidity sensors shall continuously send their signals to the control cabinet for processing and indication.

 

2.               On a signal indicating a requirement for humidity, the humidifier shall read the feed water conductivity and initiate the diagnostic sequence. Upon completion, the conductivity shall be entered into memory to control the cylinder flushing cycle and the power contactor shall be energized. The fill valve shall be activated as required to reach output and replenish water being boiled off or drained.

 

3.               If the current exceeds the maximum level, due to warming of the water in the steam generating cylinder, the humidifier shall automatically drain to reduce the current to the setpoint level.

 

4.               If the water is of low conductivity, the humidifier will automatically annunciate a special low conductivity startup algorithm which will concentrate the minerals to permit output capacity to be reached sooner.

 

5.               If the humidifier is operating on proportional control, it shall track with the control signal, filling and draining as required to supply the humidity requirements. Tracking with the signal shall be immediate, without delay.

 

6.               The humidifier shall incorporate "adaptive intelligence" to prevent it from hunting and reduce fluctuations to minimum automatically zeroing to the setpoint and maintaining precise chemistry control in the steam generating cylinder.

 

7.               The humidifier shall automatically control the cylinder chemistry to prevent premature plate out of the minerals on the electrodes, and through precise chemical control shall help to keep the drain lines clean. The unit shall indicate when the cylinder is approaching the end of its useful life, but without shutting down.

 

III.            EXECUTION

 

A.    General

 

1.               Install the humidifiers as detailed in the installation drawings and schedules and/or as recommended by the manufacturer.

 

2.               Manufacturer to furnish complete submittal drawings before installation and operating manuals after.

 

3.               Humidifiers shall be the DGH-Carel SD 2000 series electronic steam humidifiers as manufactured and distributed by:

 