Industrial and Commercial Humidifiers
    and OEM HVAC/R Controls

 
AIR CONDITIONING CONTROLS REFRIGERATION CONTROLS HUMIDIFIERS
KSA Helpful Links Easytools Case Studies Remote Management BMS Interfaces
 
  Temperature / Humidity Sensors - Specifications
Room and duct active sensors - ASW* - ASD*
Mounting Drawing Electric Drawing Dimentions Drawing Overview Drawing Not Available
Technical Data
Power supply 9 to 30 Vdc or 12 to 24 Vac (-10% to 15%), 50/60 Hz
ASWC112000: 24 Vac/dc (-10% to 15%), 50/60 Hz
Operating Conditions ASWH*: 14 to 158°F (-10 to 70°C), 10 to 90% RH non-condensing
ASWT*: 14 to 158°F (-10 to 70°C), 10 to 90% RH non-condensing
ASWC*: 32 to 122°F (0 to 50°C), 10 to 90% RH non-condensing
Storage Conditions ASW:-4 to 158°F (-20 to 70°C), <90% RH non-condensing
ASD: 14 to 158°F (-10 to 70°C), <90% RH non-condensing
Range ASWH*: 10 to 90% RH
ASWT*: 14 to 158°F (-10 to 70°C)
ASWC*: 32 to 122°F (0 to 50°C), 10 to 90% RH non-condensing
ASDH1*: 10 to 90% RH; 10
ASDT*: 14 to 158°F (-10 to 70°C)
ASDC111*: 32 to 122°F (0 to 50°C), 10 to 90%
ASDC230*: 14 to 158°F (-10 to 70°C), 10 to 100%
Precision ASWH*: 77°F (25°C): ±3%; 32 to 122°F (0 to 50°C): ±6%
ASWT030*: 77°F(25°C): ±0.36°F(0.2°C); 14 to 158°F(-10 to 70°C): ±0.26°F(0.7°C)
ASWT011*: 77°F(25°C): ±0.45°F(0.25°C); 32 to 122°F(0 to 50°C): ±0.9°F(0.5°C)
ASWC110*: Temperature: 77°F(25°C): ±0.72°F(0.4°C), 32 to 122°F(0 to 50°C): ±0.9°F(1.2°C) - Humidity: 77°F(25°C): ±3%; 32 to 122°F(0 to 50°C): ±6%
ASWC111*: Temperature: 77°F(25°C): ±0.45°F(0.25°C), 32°F to 122°F(0 to 50°C): ±0.9°F(0.5°C); Humidity: 77°F(25°C): ±3%, 32°F to 122°F(0 to 50°C): ±6%
ASWC112*: Temperature: 77°F(25°C): ±0.72°F(0.4°C); 32°F to 122°F(0 to 50°F): ±2.16°F(1.2°C); Humidity: 77°F(25°C): ±3%; 32°F to 122°F(0 to 50°C): ±6%
ASDH1*: 77°F(25°C): ±3%; 32 to 122°F(0 to 50°C): ±6%; ASDH2*: 77°F(25°C): ±3%; 14 to 158°F(-10 to 70°C): ±5%
ASDT030*: 77°F(25°C): ±0.36°F(0.2°C); 14 to 158°F(-10 to 70°C): ±1.26°F(0.7°C)
ASDT011*: 77°F(25°C): ±0.45°F(0.25°C); 32 to 122°F(0 to 50°C): ±0.9°F(0.5°C)
ASDC111*: Temperature: 77°F(25°C): ±0.45°F(0.25°C); 32 to 122°F(0 to 50°C): ±0.9°F(0.5°C); Humidity: 77°F(25°C): ±3%; 32 to 122°F(0 to 50°C): ±6%
ASDC230*: Temperature: 77°F(25°C); ±0.36°F(0.2°C); 14 to 158°F(-10 to 70°C): ±2.16°F(1.2°C); Humidity: 77°F(25°C): ±3%; 14 to 158°F(-10 to 70°C): ±5%
Output Signals ASWH*: 0 to 1 V; 4 to 20 mA
ASWT*: NTC res. (compatible guide) or 0 to 1 V; 4 to 20 mA
ASWC*: 0 to 1 V; 4 to 20 mA; ASWC112*: 0 to 10 V; 0 to 1 V; 4 to 20 mA
ASDH*: 0 to 1 V; 4 to 20 mA
ASDT*: NTC res. (compatible guide) or 0 to 1 V; 4 to 20 mA
ASDC*: 0 to 1 V; 4 to 20 mA
Time Constant ASWH*: 60 s (still air); 20 s (9.8 ft/s (3 m/s))
ASWT030*: 250 s (still air); 25 s (9.8 ft/s (3 m/s))
ASWT011*: 300 s (still air); 110 s (9.8 ft/s (3 m/s))
ASWC*: Temperature: 250 s (still air); 25 s (9.8 ft/s (3 m/s)) Humidity: 60 s (still air); 20 s (9.8 ft/s (3 m/s))
ASDH*: 15 s (still air); 10 s (9.8 ft/s (3 m/s))
ASDT030*: 200 s (still air); 60 s (9.8 ft/s (3 m/s))
ASDT011*: 300 s (still air); 120 s (9.8 ft/s (3 m/s))
ASDC*: Temperature: 200 s (still air); 60 s (9.8 ft/s (3 m/s)); Humidity: 15 s (still air); 10 s (9.8 ft/s (3 m/s))
Index of protection IP30
 
Industrial environments active sensors - ASP*
Mounting Drawing Electric Drawing Dimentions Drawing Overview Drawing Not Available
Technical Data
Power supply 9 to 30 Vdc or 12 to 24 Vac (-10% to +15%), 50/60 Hz

Operating Conditions

ASPT*: 14°F to 158°F(-10 to 70°C), <90% RH non-condensing
ASPC11*: 32 °F to 122°F(0 to 50°C), 10 to 90% RH non-condensing
ASPC23*: 14°F to 158°F(-10 to 70°C), 0 to 100% RH non-condensing
Storage Conditions -4°F to 158°F(-20 to 70°C), <100% RH non-condensing
Range ASPT*: 14°F to 158°F(-10 to 70°C)
ASPC11*: 32°F to 122°F(0 to 50°C), 10 to 90% RH
ASPC23*: 14°F to 158°F(-10 to 70°C), 0 to 100% RH
Precision ASPT*: 77°F(25°C): ±0.45°F(0.25°C); 32 to 122°F(0 to 50°C): ±0.9°F(0.5°C)
ASPC11*: Temperature: 77°F(25°C): ±0.72°F(0.4°C); 32 to 122°F(0 to 50°C): ±2.16°F(1.2°C); Humidity: 77°F(25°C): ±3%; 32 to 122°F(0 to 50°C): ±6%
ASPC23*: Temperature: 77°F(25°C): ±0.36°F(0.2°C); 14 to 158°F(-10 to 70°C): ±2.16°F(1.2°C); Humidity: 77°F(25°C): ±3%; 14 to 158°F(-10 to 70°C): ±5%
Output Signals 0 to 1 V; 4 to 20 mA
Time Constant ASPT*: 330 s (still air); 200 s (9.8 ft/s (3 m/s))
ASPC*: Temperature: 330 s (still air); 200 s (9.8 ft/s (3 m/s)); Humidity: 20 s (still air); 15 s (9.8 ft/s (3 m/s))
Index of protection IP55 (case); IP54 (sensor)
 
Active immersion sensors - ASIT030000
Mounting Drawing Electric Drawing Dimentions Drawing Overview Drawing Not Available
Technical Data
Power supply 9 to 30 Vdc or 12 to 24 Vac (-10% to +15%), 50/60 Hz
Operating Conditions 14 to 158°F(-10 to 70°C), <90% RH non-condensing
Storage Conditions -4 to 158°F(-20 to 70°C), <90% RH non-condensing
Range -22 to 194°F(-30 to 194°C)
Precision 77°F(25°C): ±0.9°F(0.5°C); -22 to 194°F(-30 to 90°C): ±1.8°F(1°C)
Output Signals -0.3 to 1 V; 4 to 20 mA
Time Constant 200 s (still air); 45 s (9.8 ft/s (3 m/s))
Index of protection IP55 (case); IP67 (sensor)
 
Universal active sensors - ASET*
Mounting Drawing Electric Drawing Dimentions Drawing Overview Drawing Not Available
Technical Data
Power supply 9 to 30 Vdc or 12 to 24 Vac (-10% to +15%), 50/60 Hz
Operating Conditions 14 to 158°F(-10 to 70°C), <90% RH non-condensing
Storage Conditions -4 to 158°F(-20 to 70°C), <90% RH non-condensing
Range ASET03*0 and ASET03*1: -22 to 194°F(-30 to 90°C)
ASET03*2: -22 to 302°F(-30 to 150°C)
Precision ASET03*0 and ASET03*1: 77°F: ±0.9°F; -22 to 194°F: ±1.8°F  (25°C: ±0.5°C; -30 to 90°C: ±1°C)
ASET03*2: 77°F ±0.9°F; -22°F to 302°F ±3.06°F
(25°C: ±0.5°C; -30 to 150°C: ±1.7°C)
Output Signals ASET03*0 and ASET03*1: -0.3 to 1 V; 4 to 20 mA
ASET03*2: -0.3 to 1.5 V; 4 to 20 mA
Time Constant 200 s (still air); 45 s (9.8 ft/s (3 m/s))
Index of protection IP55 (case); IP67 (sensor)
 
NTC
Mounting Drawing Not Available Electric Drawing Not Available Dimentions Drawing Overview Drawing Not Available
Technical Data
NTCO*HP00  
Storage Conditions -58 to 221°F (-50 to 105°C)
Range -58 to 221°F (-50 to 105°C) in air;
-58 to 122°F (-50 to 50°C) in fluid
Precision 77°F (25°C): ±1%
Time Constant 75 s (in air)
Index of protection IP67 (sensor)
   
NTCO*WF00  
Storage Conditions -58 to 221°F (-50 to 105°C)
Range -58 to 221°F (-50 to 105°C)
Precision 77°F (25°C): ±1%
Time Constant 4.5 s (in air)
Index of protection IP68 (sensor)
   
NTCO*WP00  
Storage Conditions -58 to 221°F (-50 to 105°C)
Range -58 to 221°F (-50 to 105°C)
Precision 77°F (25°C): ±1%
Time Constant 10 s (in air)
Index of protection IP68 (sensor)
 
PT100
Mounting Drawing Not Available Electric Drawing Not Available Dimentions Drawing Overview Drawing Not Available
Technical Data
Range PT100*A1: -94 to 482°F (-70 to 250°C)
PT100*A2: -58 to 752°F (-50 to 400°C)
PT100*A3: -58 to 392°F (-50 to 200°C)
TSP1001B10: 14 to 392°F (-10 to 200°C)
Precision B DIN class, according to DIN-IEC751 standard
Index of protection PT100*: IP65
TSP1001B01: IP67
 
PT1000 - TSH* / TSQ*
Mounting Drawing Not Available Electric Drawing Not Available Dimentions Drawing Overview Drawing Not Available
Technical Data
Storage Conditions -58 to 194°F (-50 to 90°C)
Range -58 to 482°F (-50 to 250°C)
Precision IEC 751 B class
Time Constants 2.5 s (in air)
Index of protection IP67 (sensor)
» product overview
» part number
» specification
» literature
 
 
Copyright © 2006 CAREL USA. All Rights Reserved.
Home     Contact Us    Careers    Sitemap